Installations with more than 64 addresses can be implemented by networking up to 12 Light Server 64+ units via the integrated Ethernet interface. This allows up to 12x64=768 DALI addresses to be handled. Two Light Servers 64+ can be directly connected using a network cable. More than two Light Servers 64+ are networked using one or several Ethernet hubs and a Cat5 cable. Several Ethernet hubs in large installations can be cascaded. The lines of the connections to the Ethernet hub can have a length of up to 100m, so that Light Servers do not need to be arranged right next to each other.