Light impact and luminaire arrangements

Light for large surfaces: room height 5-10m

The visual comfort of the lighting is important in high rooms. Narrow distribution downlights are suitable for uniform general lighting.

General lighting

For wide-area horizontal general lighting, high rooms with ceiling heights of 5-10m require high lumen-output downlights with especially good glare control to ensure high levels of visual comfort. The diameter of the light beam becomes proportionally wider over its distance, and for this reason narrower beam angles such as flood or wide flood should be specified for high rooms.

Rule of thumb for luminaire arrangement

The following rule of thumb applies for arranging luminaires with flood and wide flood light distribution in rooms with heights of 5-10m: The spacing between luminaires (d) should not be wider than the height of the luminaires above the working plane (h) to achieve uniform horizontal lighting. d ≤ 0,5 x h a = d